| ANALOGUE INPUTS
|
- Voltage
|
0 - 10 V |
- Current
|
4 - 20 mA ou 0 - 20 mA |
- Resistance board
|
PT 100 |
- Resolution
|
14 bits |
- Accuracy
|
10 -3 Full scale at 20°C |
- Conversion time
|
approximately 60 ms |
- Filtering
|
20 ms per channel |
- Transducer power supply
|
12 VDC (10 mA/channel)
Can be set (1 to 5 s) |
|
| NUMERICAL PULSE
INPUTS |
- Floating contact inputs
|
(i.e. with no potential)
or at 0 to 5 VDC |
- Filtering
|
5 ms per channel |
- Count frequency
|
< 100 pulse per second |
- Encoder resolution
|
100 points/turn |
- Encoder speed
|
100 points per second |
- Transducer power supply
|
5 VDC (20 mA) |
|
| ON/OFF INPUTS
|
- Inputs for floating contacts
|
(i.e. with no potential) |
- Filtering
|
20 ms per channel |
|
| ON/OFF OUTPUTS
|
- Relay Contact
|
One Make contact (floating) |
- Voltage
|
< 240 VAC |
- Current
|
< 8 A |
|
| COMMUNICATION
INTERFACE |
- Digital interface
|
RS 232 C |
- Format
|
7 bits, 1 stop, even parity
8 bits, 1 stop, without parity can be set |
- Transmission speeds
|
1200, 2400, 4800 and 9600
Bauds can be set |
|
| POWER SUPPLY
|
- Nominal voltage
|
12 VDC |
- Variable over a rang
|
between 9 and 36 VDC |
- Current drain
|
< 100 mA in operation
< 3 mA in standby |
|
| DATA STORAGE
|
- RAM
|
|
- Module sizes
|
128, 256, 640 Kbytes |
|
| RUNNING PARAMETERS
|
- Sampling period
|
5 s to 24 h |
- Recording period
|
5 s to 24 h |
- Filtering
|
Linear average |
- Thresholds high or low
|
at between 0 and 100%
of data range |
- Transducer supply
|
1 to 5 s |
|
| CONVERSION CURVES
|
- Linear interpolation
|
y = Ax + B |
- Non-linear interpolation
|
y = Ax3/2 + Bx5/2 |
- Temperature compensation
|
z = (A + By)x |
- Linear combinaison
|
z = Ax + By |
- Experimental curves
|
20 points |
|
| HOUSING PAINTED
METAL BOX |
- Dimensions
|
200 x 122 x 68 mm |
- Protection index
|
IP 40 |
|
| HOUSING PLASTIC
ENCLOSURE |
- Dimensions
|
280 x 280 x 120 mm |
- Protection index
|
IP 65 |
|
| RUNNING RANGE
|
- Temperature from
|
-20°C to +55°C
There is a version for the range -40°C to +60°C |
- Relative humidity
|
< 80% without condensation |
|
| STANDARDS/DIRECTIVES
|
- CE Mark
|
|
- EMC C46-023 or 801-4
|
Level 3 protection tests |
|
CAN BE USED WITH
SERIES 3000
- Transmitters
Alphée 3100/3200 and inductive probes
Alphée 3120/3220
- Bubbler
gauge Alphée 3010/3020
|
|